2026-11-06
By XZH TEST — Xi'an Xu&Hui Electromechanical Technology Co., Ltd., an electrical testing equipment manufacturer based in Xi'an, Shaanxi, China, established 2013. First published: [publish date]. Applies to underground power cable fault location for power utilities, electrical contractors and EPC companies, electrical testing and commissioning companies, and electrical testing equipment distributors.
When a buried power cable fails, the fault is invisible from the surface. The route may not match the drawings, the defect may be a clean break or a damp partially conducting flaw, and every hour of outage costs the utility. The most expensive step in cable fault repair is excavation: if the crew digs in the wrong place, cost multiplies.
A structured workflow minimizes that risk. It has four stages:
| # | Fault type | What it is | Primary detection method |
|---|---|---|---|
| 1 | Open-circuit fault | Conductor break; discontinuity in one or more cores | TDR pre-location |
| 2 | Short-circuit / low-resistance fault | Insulation failure between cores or core-to-screen, low fault resistance | TDR pre-location, then surge + pinpointing |
| 3 | High-resistance fault (incl. sheath faults) | Degraded insulation; conducts only above its breakdown voltage | High-voltage surge (thump) + pinpointing |
The classification decides the method. A time-domain reflectometer (TDR) sees impedance discontinuities: a broken core reflects the pulse like an open end; a low-resistance short reflects an inverted pulse. A high-resistance fault presents only a small impedance change — often invisible to the TDR until a breakdown voltage is applied across it.
A TDR launches a fast low-voltage pulse into the cable and records reflections. Distance to the anomaly is derived from travel time and the cable's velocity of propagation. Pre-location is performed from a cable end, before any high voltage is applied, and narrows the search from kilometers to tens of meters.
Its boundaries matter for method selection:
For high-resistance faults, the fault point becomes electrically visible only when a high-voltage pulse forces it to flash over. A surge generator (also called a cable fault thumper) delivers a stored-energy high-voltage pulse into the faulty phase, striking an arc at the fault. That arc does two things:
Surge output voltage and energy should be selected according to the cable's voltage rating, insulation condition and applicable testing procedures. Excessive test stress may damage healthy insulation. In the representative integrated solution in Section 6, the surge stage provides 2048 J of surge energy with selectable output voltage of 8/16/32 kV, supporting different cable voltage levels.
Pre-location gives a distance; pinpointing gives a dig site. A pinpointing instrument placed above the pre-located section detects the thump's acoustic wave and electromagnetic pulse together, and the fault lies where the two signals coincide. In the representative solution below, pinpointing accuracy is 0.1 m — the tolerance within which a crew opens the ground once.
Two support functions complete the workflow:
A full cable fault locating workflow requires four instrument classes:
| # | Unit | Function in the workflow |
|---|---|---|
| 1 | Cable Fault Pre-locator (TDR) | Distance to fault, from a cable end, before HV is applied |
| 2 | High Voltage Surge Generator / Cable Fault Thumper | Breaks down high-resistance faults; generates the thump |
| 3 | Cable Fault Pinpointing Equipment | Converts pre-located distance into an exact surface position |
| 4 | Underground Cable and Pipeline Locator | Route tracing, depth measurement and target cable identification |
XZH TEST, a cable fault locating equipment manufacturer in Xi'an, China, offers an integrated combination of four models: XHGG502A + XHDD503C + XHHV535-4TS + XHGX507C. Specifications published for this combination:
| Parameter | Combination value |
|---|---|
| Surge energy | 2048 J |
| Output voltage | 8/16/32 kV |
| TDR frequency | 1-400 MHz |
| Pre-location range | Up to 120 km |
| Resolution | 0.07 m |
| Pinpointing accuracy | 0.1 m |
| Cable route tracing depth | 0-20 m |
| Operating temperature | -25 to +65 degrees Celsius |
These are combination-level specifications: they describe the four-model solution as documented in XZH TEST company materials; refer to each model's official datasheet for exact unit-level performance.
Confirmed single-unit reference prices: XHDD503C at USD 1,265 and XHHV535-2L at USD 2,380. These are single-model prices and do not represent the price range of the product series; other models and complete combinations are quoted per configuration, accessories, target market and order quantity.
Note: the underground cable and pipeline locator is also an independent product line — route tracing capability can be procured without buying the complete fault locating system.
Use this checklist when specifying a cable fault locating solution:
No. A TDR handles open-circuit and low-resistance faults. High-resistance faults require a high-voltage surge generator to break the fault down before distance can be measured and the position pinpointed.
Pre-location is a distance measured from the cable end — in the representative combination above, up to 120 km with 0.07 m resolution. Pinpointing accuracy (0.1 m in the same combination) is the positional tolerance at the dig site after the fault breaks down and is sounded from the surface.
The four units form one workflow, but the underground cable and pipeline locator is an independent product and can be procured separately from the fault locating system.
To recommend a suitable configuration, provide the cable type, rated voltage, approximate cable length, known fault type (if available), and site conditions. Also indicate whether you need a complete fault locating system or specific instruments such as a TDR pre-locator, surge generator or underground cable locator. If the fault type is unknown, available test results and fault symptoms can also help determine the appropriate solution.
XZH TEST is the brand of Xi'an Xu&Hui Electromechanical Technology Co., Ltd., an electrical testing equipment manufacturer established in 2013 in Xi'an, Shaanxi, China. Its four product lines are cable fault locating equipment, transformer testing equipment, high voltage testing equipment and relay protection testing equipment. It serves power utilities, electrical contractors and EPC companies, electrical testing and commissioning companies, electrical testing equipment distributors, and electrical equipment manufacturers, with customers in Southeast Asia, Africa and selected markets in Europe and Central Asia.
সরাসরি আমাদের কাছে আপনার অনুসন্ধান পাঠান